HomeMy WebLinkAboutResolution #3249
RESOLUTION NO. 3249
A RESOLUTION APPROVING AN AGREEMENT BETWEEN THE CITY OF CANTON AND
CENTRAL ILLINOIS PUBLIC SERVICE COMPANY AND DIRECTING THE MAYOR TO
EXECUTE AND DELIVER SAID AGREEMENT ON BEHALF OF THE CITY OF
CANTON, ILLINOIS.
WHEREAS, the City of Canton is installing a standby
generator at the David W. O'Brien Public Safety Building; and,
WHEREAS, the Canton City Council of the City of Canton has
determined that it is necessary and in the best interest of the
City of Canton to enter into an agreement for electric standy use
relating to the use of the standby generator at the David W.
O'Brien Public Safety Building, hereto attached and herein
incorporated as Exhibit "A".
NON, THEREFORE, BE IT RESOLVED BY THE CITY COUNCIL OF THE
CITY OF CANTON, Fulton County, Illinois as follows:
1. That the agreement for electric standby use, hereto
attached as Exhibit "A" between the City of Canton and Central
Illinois Public Service Company, is hereby approved.
2. That the Mayor is hereby authorized and directed to
execute and deliver said agreement on behalf of the City of
Canton, Illinois.
3. That this Resolution shall be in full force and effect
immediately upon its passage by the City Council of the City of
Canton, Illinois.
PASSED by the City Council of the City of Canton, Fulton
County, Illinois at a regular meeting this 6th day of September,
1994, upon a roll call vote as follows:
AYES: A]-dennen ~P~> made, Sarff, Phillips, P~lleck.
NAYS: None.
ABSENT: Aldercr~en May, Meade, Coay.
APPROVED:
~~~
ona war s, ayor
ATTEST:
v
i
arr ~ W i to City Clerk
i
A-2313 11/93
ELECTRIC STANDBY 115E AC~tEE)ENT
(Alternate Source Art. 700, 7D7 and/or 702 by Custa~er)
AfAtEEMENT, made this day of 1994, by and between CENTRAL ILLINOIS PIBLIC SERVICE
COIPANY, hereinafter called "Company", and the City of Canton hereinafter called "Customer",
YITMESSETH:
1. Customer desires to use a standby system in connection with the electric public utility service required by
Customer in operation of Customer's Police and Fire Building and 911 System located at First & Spruce,
Canton Fulton County, Illinois.
2. Customer hereby attests that the standby system will be operated as defined under Articles 700, 701
and/or 702 of the current edition of the National Electrical Code, and that said facilities will be operated as
indicated below:
A) Whereas alternate source is used only to provide standby service in the event of the failure of Company's
service, system testing will be allowed as outlined within Section 700-4 and 701-5 of the current edition of
the National Electrical Code. All testing will be for the purpose of assuring that Customer's facilities are
in proper operating condition.
3. Customer shall provide and install a double-throw switch and/or Kirk Key Interlock System at Customer's expense
on load side of Company's metering equipment located at Customer's said Police and Fire Building
Said double-throw switch and/or Kirk Key Interlock System shall be used
for transferring Customer's electric toad from Company's source of supply to Customer's alternate source of supply.
4. The double throw switch and/or Kirk Key Interlock System shall be approved by Company and shall be so designed,
installed and maintained that visual inspection of actual electrical contact can be readily and conveniently made. The
switch(es) shall be of suitable voltage, phase, current and interrupting rating for the type of service supplied by
Company to Customer's facilities.
5. The installation shall be made in such a manner that Customer's standby system cannot under any circumstances
be operated in parallel with Company's service or energize any of Company's facilities.
6. Customer shall provide to Company a single line diagram which shall be inspected and approved by Company
before Customer's standby system is placed in operation. Said diagram shall, at a minimum, clearly define the location
of Company's metering equipment, Customer's main switch, Customer's transfer equipment and Customer's alternate
source. Said diagram shall become part of this Agreement. Any modification of Customer's electrical distribution
system which would change the electrical location of the items on the approved single Line diagram would require
Customer to submit to Company a revised single line diagram for Company's inspection and approval.
7. The installation of the alternate source, the double-throw switch and/or Kirk Key Interlock System, together
with all auxiliary devices, shall be inspected and approved by Company before the facilities are placed in operation.
The Kirk Key Interlock System shall only be approved for use by industrial and larger commercial customers.
8. Company may make periodic inspections to ensure compliance with these requirements. Modification or
replacement of the double-throw switch and/or Kirk Key Interlock System of an approved installation shall be made only
"after approval by Company.
9. Company shall not be liable for any loss or damage to Customer occasioned by the use of said standby system.
Customer shall be liable for any loss or damage to Company resulting from the use of said standby system. Customer
shall indemnify and hold Company harmless against all claims, demands, suits or judgements made, brought, or obtained
by third parties against Company occasioned by the use of Customer's standby system.
YRITTEN MDDIFIGTION. After its execution this Agreement shalt not be modified except in writing executed by both
parties, making express reference to this Agreement and the specific provision hereof modified or amended.
IN YITNESS YHEREOF, the parties hereto have caused this agreement to be executed in duplicate, in person or by its
duly authorized officers or agents, day and year first above written.
CENTRAL ILLINOIS PUBLIC SERVICE COMPANY
(Customer)
By
(Authorized Company Representative Signature)
(Name)
(Title)
Submitted By
Jim Wood
By
(Authorized Customer Representative Signature)
(Name)
(Title)
Account No. 08-240-180-2995-1